UPS ATLANTIS A03-OP2002P 2000VA/1800W DOPPIA CONVERS.,FORMA D'ONDA SINUSOIDALE,TOWER, SMART BATTERY MANAG.-QUATTRO BATT.12V 9A/H

A03-OP2002P

Cod. Articolo V12126

645,49 €
Tasse incluse Spedito entro 2-4 giorni
Quantità
Ultimi articoli in magazzino

Descrizione

Power Rating (VA): 2000

Power Rating (W): 1800

Input:

- 80VAC-300VAC (load <=30%±5%)

- 120VAC-300VAC (load <=60%±5%)

- 140VAC-300VAC (load <=80%±5%)

- 160VAC-300VAC (load <=100%±5%)

Frequency Range: 40Hz to 70Hz

Power Factor: >0,99 (Normal Voltage)

Output:

- Voltage: 208/220/230/240VAC

- AC Voltage Regulation: ±1% 

- Frequency Range: 50Hz (±0.5%) or 60Hz (±0.5%)

- Waveform: Pure SineWave

- Crest Ratio Current 3:1 (Max)

- Harmonic Distortion (THDU): min 3% THD (liner Load) / min 5% THD (Non liner Load)

Transfer:

- AC->Battery: Zero

- INV->ByPass: Less than 4ms (typical)

WaveForm (Batt. Mode): Pure Sinewave

Efficiency

- AC Mode = 90%

- Battery = 87%

- ECO = 97%

Battery:

- Voltage: 48VDC

- Capacity: 12V/9.0Ah

- Quantity: 4

- Recharge Time: 4 hours to (90%)

- Type: Sealed Maintenance Free Lead Acid VRLA Type

- Design: Swappable battery design

- Charging Voltage: 54,8VDC ±1%

- Charging Current: 1.5A Max

Indicators (display LCD):

- UPS status, Load level, Battery level, Input/Output/battery info, Discharge time and Fault indicators

Backup Time:

- 1800w up to 3:15m

- 1350w up to 5:30m

- 900w up to 9:30m

- 450w up to 22m

Protection:

- 105% < Overload AC <110% Overload Warning UPS Only

- 110% < Overload AC <130% Overload Warning UPS transfers to ByPass after 1 minutes

- Overload AC >130% Overload Warning UPS transfers to ByPass after 3 seconds

- 105% < Overload Battery <110% Overload Warning UPS

- 110% < Overload Battery <130% Overload Warning UPS shut down after 1 minute

- Overload AC >130% Overload Warning shut down after 3 seconds

- 110% < ByPass <120% Overload Warning UPS shut down after 30 minutes

- 120% < ByPass <130% Overload Warning UPS shut down after 10 minutes

- ByPass >130% Overload Warning UPS shut down after 1 minute

- Overload Inverter (>100%)

- Short Circuit INV: Electric Circuit

- Short Circuit AC: ICB & Electric Circuit

- Battery Over-drain Two stages: Controlled Battery Low Warning & Cut Off

- High Surge Level Immunity (>7KV)

Advanced: Fan detect protection and Fan speed control | ECO mode

Connections:

- Output 4xIEC 320 C13 (Battery Power Supplied)

- RS232 and USB(HID)

- Intelligent Slot for SNMP Card

- EPO/ROO

- Battery Bank Connection

Dimensions (WxHxD): 151 x 225 x 394 mm

Net Weight 17,15 Kg (with Battery)

Temperature: 0°-40° C

Humidity: Humidity 20-90% (non-condensing)

Noise level: Less then 50 dBA @ 1.0 meter (battery full charged, without buzzer)

Dettagli del prodotto
A03-OP2002P
1 Articolo

16 altri prodotti della stessa categoria: